data center
Overview
MMC data centre is located at Computer Exchange 2 (CX2) in Cyberjaya, Malaysia. A purpose built data centre with a net data center space of 157,500 sq, ft., complete with multiple back-up power generation and Uninterruptible power supply N+1 with 15 minutes battery reserve and fire detection and suppression.
Features & Facilities
1. Superlative building features
| Tier 3 facility designed for high redundancy and concurrent maintenance |
| Sunken floor design of 1000mm depth |
| Cast in-situ post tension flat slab construction (10kN/m2 floor loading) |
| 4800mm slab to slab with floor to ceiling height of 4590mm |
| Insulated walls for energy efficiency |
| Double slab roof with 3 layers of waterproofing |
| Roof top reinforced for wireless antennae installation |
| Critical power provision from 30W/ft2 to 150W/ft2 with associated precision cooling |
| 2 x 33 KV Feeders from 2 switch yards, capable of supporting up to 30 MW power per feeder |
| Up to 8 nos of Transformers (26 MVA capacity) |
| Up to 12 x 2.0 MVA Generator sets, 144,500 litres diesel (2x65,000 underground /14,500 day tank) |
| Up to 54 sets of 400 kVA UPS systems (total of 21.6 MVA) |
| HSSD for early detection, addressable detectors and Water mist (clean agent) for fire suppression |
| Total building and power monitoring systems |
| Multiple Lift transports to support human and equipment traffic and movement |
| 69 points (Greenmark Gold Plus) as Benchmarked against BCA Greenmark |
| |
|
2. Superlative facilities provided
Electrical Services
| - |
Multiple layers of power backup equipment with redundant connections from each layer. |
| - |
N+1 redundancy in all electrical design and equipments. |
|
Room Environment
| - |
N+1 Air-cooled Precision air conditioning with raised floor as air plenum to maintain environment at optimum temperature and humidity of 22ΊC and 50% RH. |
|
Fire & Safety
| - |
High sensitivity smoke detection system. |
| - |
Double knock fire detection and alarm system. |
| - |
Water Mist System as the fire extinguishing system at computer floor. Water mist is fast, efficient and totally safe for human, environment and equipment. |
|
Security System
| - |
State of the art security with limited access to computer floors. |
| - |
Mantrap system. |
| - |
Controlled access for Maintenance personnel. |
|
Network Services
| - |
Telco Neutral with Multiple Backbone Service Providers for Network Redundancy. |
|
Command Centre
| - |
Monitor and control the buildings facilities that includes electrical, power generators, fire system, environment, access control, surveillance, etc. |
|
| |
|